CIH, CIK & CIL HRCI-MISC
Description: HRI fuses provide both overload and short-circuit protection, featuring offset blades for bolt down mounting.
Construction: Ceramic body.
Ratings:
Volts: 600V
Amps: 1-100A
IR: 200kA@600V
Agency Information: CE, CSA C22.2 No. 106 M92.
Dimensional Data
(The CIL14 has a rejection hole, not a slot as shown above.)
Ratings, Categories and Dimensions
Current Ratings (Amps) | Catalog Number | Dimensions in Inches and (mm) | ||||||||||
A MAX | B MAX | C MAX | D NOM | E NOM | F NOM | G NOM | H NOM | J MAX | K NOM | L MAX | ||
1 | 1CIH07B | 2.25 (57) | 0.94 (24) | 3.38 (86) | 0.38 (9.2) | 0.04 (1) | 2.88 (73) | 0.21 (5.2) | 0.31 (8) | 1 (25.4) | 0.1 (2.6) | 2.38 (60) |
3 | 3CIH07B | |||||||||||
6 | 6CIH07B | |||||||||||
10 | 10CIH07B | |||||||||||
15 | 15CIH07B | |||||||||||
20 | 20CIH07B | |||||||||||
25 | 25CIH07B | |||||||||||
30 | 30CIH07B | |||||||||||
35 | 35CIK07B | 2.28 (58) | 1.06 (27) | 3.56 (91) | 0.5 (12.7) | 0.05 (1.2) | 2.88 (73) | 0.21 (5.2) | 0.41 (10.5) | 1.09 (28) | 0.13 (3.2) | 2.38 (61) |
40 | 40CIK07B | |||||||||||
50 | 50CIK07B | |||||||||||
60 | 60CIK07B | |||||||||||
80 | 80CIL14B | 2.75 (70) | 1.44 (37) | 4.38 (111) | 0.75 (19) | 0.09 (2.5) | 3.69 (94) | 0.34 (8.7) | 0.41 (10.5) | 1.5 (38.5) | - | 2.91 (74) |
90 | 90CIL14B | |||||||||||
100 | 100CIL14B |
Motor Branch Circuit Application Guide
Buss HRCI-MISC Fuse Rating | Full Voltage Starting | Reduced Voltage Starting | |
Normal Duty | Heavy Duty | ||
Maximum Full Load Current of Motor | |||
3CIH07B | 0.75 | 0.64 | 1.3 |
6CIH07B | 1.6 | 1.3 | 2.6 |
10CIH07B | 2.5 | 2.1 | 4 |
15CIH07B | 5 | 4 | 7.7 |
20CIH07B | 7.3 | 5.9 | 11 |
25CIH07B | 10 | 8 | 15 |
30CIH07B | 12 | 9.9 | 19 |
35CIK07B | 14 | 11 | 21 |
40CIK07B | 16 | 13 | 25 |
45CIK07B | 18 | 14 | 27 |
50CIK07B | 22 | 17 | 31 |
60CIK07B | 27 | 21 | 39 |
70CIL14B | 32 | 26 | 49 |
80CIL14B | 40 | 31 | 60 |
90CIL14B | 44 | 35 | 66 |
100CIL14B | 53 | 41 | 77 |
Recommended Fuse Holders
Fuse | Fuse Holder |
1-30A | CM30CF |
35-60A | CM60CF |
Time/Current-Curves
Energy Let-Through Curves
Peak Let-Through Curves