ET-British BS 88 690V 25-80A

  
Description:
BS 88 style stud-mount fuses.

Ratings:
Volts: 690Vac/500Vdc
Amps: 6-710A
IR: 200kA RMS Sym.

Agency Information: CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized. Consult Cooper Bussmann for UL Recognition status.

Electrical Characteristics
Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).

Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.

Power Losses

Watts loss at rated current is given in the electrical characteristics.
The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

Features and Benefits
• Excellent cycling capability
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters

Dimensions (mm)


Catalog Numbers
Catalog Numbers Type Rated Current RMS-Amps I2t(A2 Sec) Watts Loss
Pre-arc Clearing
at 415V at 660V
25ET ET 25 25 150 250 7
32ET 32 32 190 350 11
35ET 35 52 310 500 11
40ET 40 103 600 900 9
45ET 45 103 680 1100 11
56ET 56 135 950 1500 14
63ET 63 171 1200 2000 16
80ET 80 360 2500 4000 18


• Watts loss provided at rated current.
• Note: FC, 8ET, 12ET, 15ET, 20ET, 65EET and 75EET are available for replacement purposes on existing equipment.

Time-Current Curve

Peak Let-Through Curve

----------------------------------