FEE-British BS 88 690V 100-200A

  
Description:
BS 88 style stud-mount fuses.

Ratings:
Volts: 690Vac/500Vdc
Amps: 6-710A
IR: 200kA RMS Sym.

Agency Information:
CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized. Consult Cooper Bussmann for UL Recognition status.

Electrical Characteristics
Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by
correction factor, K, given as a function of applied working voltage, Eg, (rms).

Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.

Power Losses

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

Features and Benefits
• Excellent cycling capability
• Excellent dc performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters

Dimensions (mm)


Catalog Numbers
Catalog Numbers Type Rated Current RMS-Amps I2t(A2 Sec) Watts Loss
Pre-arc Clearing
at 415V at 660V
100FEE FEE 100 400 1600 2400 24
120FEE 120 540 1900 3100 32
140FEE 140 850 2500 3800 36
160FEE 160 1000 3700 5700 46
180FEE 180 1400 5300 8400 46
200FEE 200 1900 7100 11400 52
• Watts loss provided at rated current.

Time-Current Curve


Peak Let-Through Curve

----------------------------------