We are professional in EATON BUSSMANN (Formerly Cooper Bussmann).

cooper bussmann

FWP 700V North American High Speed Fuse

  
Description:
North American style stud-mount fuses.

Ratings:
Volts: 700Vac/dc
Amps: 5-1200A
IR: 200kA RMS Sym. 50kA @700Vdc

Agency Information: CE, UL Recognition & CSA Component Acceptance on 5-800A

Electrical Characteristics
Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).

Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.

Power Losses

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Superior cycling capability

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters

Dimensions (in)
Order # Fig. A B C D E F G H J
FWP-5B-30B 1 2.87 0.563 1.855 2.477 2.477 0.25 0.405 0.063 0.25
FWP-35B-60B 1 4.375 0.813 2.75 3.708 3.312 0.344 0.725 0.125 0.542
FWP-70B-100B 1 4.406 0.947 2.594 3.625 3.563 0.344 0.75 0.125 0.375
FWP-125A-200A 1 5.09 1.5 2.84 4.19 3.5 0.41 1 0.25 0.75
FWP-225A-400A 1 5.09 2 2.84 4.28 3.53 0.41 1.5 0.25 0.78
FWP-450A-600A 1 7.09 2.5 2.84 5.72 4.19 0.53 2 0.38 1.3
FWP-700A-800A 1 6.63 2 2.844 5.562 5.062 0.625 1.5 0.25 0.875
FWP-900A-1000A 2 See Drawing
FWP-1200A 3
   


Catalog Numbers
Electrical Characteristics Ordering Information Dimensions
Type Rated Current RMS-Amps I2t (A2 Sec) Watts Loss Part Number Carton Qty. Carton Weight (lbs) Figure Number
Pre-arc Clearing at 700V
FWP 700V 5 1.6 10 1.5 FWP-5B 10 2.25 Fig.1
10 3.6 20 4 FWP-10B
15 10 75 5.5 FWP-15B
20 26 180 6 FWP-20B
25 44 340 7 FWP-25B
30 58 450 9 FWP-30B
35 34 160 12 FWP-35B 5 1.21
40 76 320 12 FWP-40B
50 135 600 12 FWP-50B
60 210 950 15.5 FWP-60B
70 305 2000 18 FWP-70B 1 0.24
80 360 2400 21 FWP-80B
90 415 2700 25 FWP-90B
100 540 3500 27 FWP-100B
125 1800 7300 28 FWP-125A 0.65
150 2900 11700 32 FWP-150A
175 4200 16700 35 FWP-175A
200 5500 22000 43 FWP-200A
225 7700 31300 45 FWP-225A 1.17
250 10500 42500 48 FWP-250A
300 17600 71200 58 FWP-300A
350 23700 95600 65 FWP-350A
400 31000 125000 78 FWP-400A
450 36400 137000 94 FWP-450A 2.39
500 45200 170000 107 FWP-500A
600 66700 250000 122 FWP-600A
700 54000 300000 125 FWP-700A 1.21
800 78000 450000 140 FWP-800A
900 91500 530000 150 FWP-900A 6.6 Fig.2
1000 120000 600000 170 FWP-1000A
1200 195000 1100000 190 FWP-1200A Fig.3
- 1 kg = 2.2 lbs 1 lb = 0.45 kg
- Interrupting rating 200kA RMS Symmetrical.
- Watts loss provided at rated current.
- (700 Vdc/Interrupting rating 50kA) U.L. Recognition & CSA Component Acceptance on 5 through 100 & 700 through 800 amperes.
- (700 Vdc/Interrupting rating 10kA) U.L. Recognition & CSA Component Acceptance on 125 through 600 amperes.

Time-Current Characteristic Curves




Peak Let-Through Cut-Off Current Characteristic Curves


----------------------------------
Products