We are professional in EATON BUSSMANN (Formerly Cooper Bussmann).

cooper bussmann

FWX 250V North American High Speed Fuse

  
FWX

Description: North American style stud-mount and flush-end fuses.

Ratings:
Volts: 250Vac/dc
Amps: 35-2500A
IR: 200kA RMS Sym.
Agency Information: CE, UL Recognized & CSA Component Acceptance on 35-800A fuses (20kA IR @250Vdc).

Electrical Characteristics
Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics.
For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).



Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.

Power Losses

Watts loss at rated current is given in the electrical char acteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp , is given as a function of the RMS load current, Ib , in % of the rated current .

Catalog Numbers
Catalog Numbers Rated Current RMS-Amps I2t(A2 Sec) Watts Loss
Pre-arc Clearingat 250V
FWX-35A 35 50 230 4.2
FWX-40A 40 60 310 5.2
FWX-45A 45 80 390 5.7
FWX-50A 50 100 520 6
FWX-60A 60 140 740 8.1
FWX-70A 70 330 1400 7.2
FWX-80A 80 430 1850 8.1
FWX-90A 90 570 2450 9
FWX-100A 100 740 3150 10
FWX-125A 125 1130 4850 12.5
FWX-150A 150 1620 6950 15.7
FWX-175A 175 2170 9300 18.5
FWX-200A 200 2790 12000 22
FWX-225A 225 3210 14700 24
FWX-250A 250 3960 18100 27
FWX-275A 275 4720 21600 31
FWX-300A 300 6000 27300 32
FWX-350A 350 10600 48600 39
FWX-400A 400 14500 66100 44
FWX-450A 450 22100 101000 49
FWX-500A 500 28000 128000 54
FWX-600A 600 41100 188000 62
FWX-700A 700 48800 190000 72
FWX-800A 800 59000 230000 84
FWX-1000AH 1000 44000 360000 100
FWX-1200AH 1200 92000 750000 103
FWX-1500AH 1500 120000 880000 140
FWX-1600AH 1600 160000 1200000 140
FWX-2000AH 2000 320000 2300000 151
FWX-2500AH 2500 670000 4700000 163
• Watts loss provided at rated current.

Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Superior cycling capability

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters

FWX 35-800A: 250V
Time-Current Curve

Peak Let-Through Curve

FWX 1000-2500A(H): 250V
Time-Current Curve

Peak Let-Through Curve
----------------------------------
Products