Specifications
Description: North American style flush-end high speed fuses.
Dimensions: See Dimensions illustrations.

Ratings:
Volts: 130Vac
Amps: 1000-4000A
IR:200kA RMS Sym.50kA @130Vdc
Agency Information: CE, UL Recognized on 1000-2000A fuses

Electrical Characteristics
Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).

Dimensions (in)



Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.

Power Losses

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The
correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

Catalog Numbers
Catalog Numbers Electrical Characteristics
Rated Current
RMS-Amps
I2T(A2 Sec) Watts Loss
Pre-arc Clearing at 130V
FWA-1000AH 1000 170000 460000 60
FWA-1200AH 1200 270000 730000 70
FWA-1500AH 1500 520000 1400000 78
FWA-2000AH 2000 860000 2400000 108
FWA-2500AH 2500 1500000 4100000 130
FWA-3000AH 3000 2100000 5700000 150
FWA-4000AH 4000 3400000 9200000 257


Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
----------------------------------
Products